optiups - Man Page
Driver for Opti-UPS (Viewsonic) UPS and Zinto D (ONLINE-USV) equipment
Synopsis
optiups -h
optiups -a UPS_NAME [OPTIONS]
Note
This man page only documents the hardware-specific features of the optiups driver. For information about the core driver, see nutupsdrv(8).
Supported Hardware
optiups was originally written against a PowerES 280es in nut-0.45. It was revised for nut-2.0.1 and tested against a PowerES 420E. It is expected to work with at least the PowerES, PowerPS, and PowerVS models.
This driver additionally supports a Zinto D from ONLINE USV-Systeme AG because of their very similar commands, but it is unknown if it also works with other UPS from them.
This driver will not work with the PowerES stock serial cable. You will need to construct your own three conductor cable:
UPS 6 -> PC 3 UPS 9 -> PC 2 UPS 4 -> PC 5
The cable for Online-USV uses pin UPS 7 (not UPS 4) ā PC 5.
Extra Arguments
This driver supports the following optional settings in the ups.conf(5) file:
- status_only
Only poll for critical status information. Without this, optiups (and all NUT drivers) poll all sorts of information from the UPS fairly often. It is probably not often enough to hurt anything, so this option probably is not very useful, unless you have a flaky serial connection or a highly loaded machine.
- nowarn_noimp
Does not print warnings when the UPS reports that a variable is not implemented or not pollable. Without the option you will get a message sent to your system logs each time NUT polls the UPS. If you specify nowarn_noimp, this message will only be logged once.
- fake_lowbatt
This forces the low battery flag true. Without it, if you want to test your UPS, you will have to unplug it and wait until the battery drops to a low/critical voltage level before NUT will respond and power down your system. With the flag, NUT should power down the system soon after you pull the plug. When you are done testing, you should remove this flag.
For basic shutdown configuration testing, the command upsmon -c fsd is preferred.
- powerup
Zinto D from ONLINE-USV cannot be identified when switched to standby. Set this flag to allow the driver to power-up your Zinto UPS. This will also power-up your equipment connected to the UPS!
Bugs
On the 420E, ups.serial and ups.temperature are unsupported features. This is not a bug in NUT or the NUT driver, just the way things are with this UPS.
Authors
- Russell Kroll
- Scott Heavner
- Matthias Goebl
See Also
The core driver
Internet resources
The NUT (Network UPS Tools) home page: https://www.networkupstools.org/