netxml-ups - Man Page

Driver for Eaton / MGE Network Management Card / Proxy (XML/HTTP Protocol) equipment

Synopsis

netxml-ups -h

netxml-ups -a UPS_NAME [OPTIONS]

Note

This man page only documents the hardware-specific features of the netxml-ups driver​. For information about the core driver, see nutupsdrv(8)​.

Supported Hardware

netxml-ups supports all recent Eaton / MGE models which use a Network Management Card or Proxy (MGE XML/HTTP protocol based)​. This applies to both Eaton (previously MGE Office Protection Systems) and to MGE UPS SYSTEMS​. Supported card and proxy models are:

Older models, such as SNMP card (Ref 66062 and Ref 66045), use the SNMP protocol and should use the snmp-ups(8) driver with the mibs=mge parameter​.

Extra Arguments

This driver supports the following optional settings in the ups.conf(5):

timeout=value

The timeout for connecting to and reading from the UPS​. Defaults to 5 seconds​. Don’t change this value unless you know exactly what you’re doing​.

This value must never be higher than half the MAXAGE value specified in upsd.conf(5), otherwise you run the risk that upsd(8) declares the driver stale while it is waiting for a connection to timeout​.

subscribe

Connect to the NMC in subscribed mode​. This allows to receive notifications and alarms more quickly, beside from the standard polling requests​.

login=value

Set the login value for authenticated mode​. This feature also needs the password argument, and allows value settings in the card​. This feature is not used yet​.

password=value

Set the password value, needed with the login for authenticated mode​. This feature is not used yet​.

shutdown_duration=value

Set the shutdown duration of the operating system, in seconds​. This represents the amount of time needed by the system to operate a clean shutdown​. Defaults to 120 seconds​.

shutdown_timer=value

Set the shutdown timer, in seconds​. After value seconds running on battery, the local system will receive a notification to shut down​. Defaults to "none" (disabled)​.

do_convert_deci

If this flag value is present, the driver assumes you have a very old MGE networked UPS (or rather an old network management card firmware) which serves certain measurements spelled 10x too big in the XML markup​.

Originally such measurements were decimated by the driver — but this is wrong for newer, more sane, devices — so this behavior was deprecated and is now disabled by default​. Enabling this flag in configuration of a particular driver instance restores the old behavior for those measurements​.

Implementation

The hostname of the networked UPS is specified with the port value in ups​.conf, i​.e​.:

[mgexml]
        driver = netxml-ups
        port = http://netxml-ups​.example​.com:80

Specifying the method to connect to the UPS (http, https) is mandatory​. If the port is equal to the default for the method specified (80 for http, 443 for https) it may be omitted​.

In order not to overload older NMCs by polling them too frequently, it is recommended to increase the "pollinterval" (see nutupsdrv(8)) and ups.conf(5)) to at least 5 seconds​.

Known Issues

HTTP(S) proxies

Don’t connect to the UPS through a proxy​. Although it would be trivial to add support for proxies, this is not recommended and don’t ask for it​. Not only because it will prevent the driver to make a persistent connection to the UPS, but also it adds an additional failure mode​. If the proxy goes down (for whatever reason), the driver will no longer be able to reach the UPS​.

Using host names for UPS NMC

An UPS network management card may be assigned a fixed/static IP address or a dynamic one (e​.g​. by DHCP) in your network​. Due to this, you may want or have to use a dynamic naming service to access the UPS​. Note that this may become a problem specifically during large outages and shutdowns, when your DHCP/DNS server might already go down while the driver needs to resolve the name involved (especially during late-shutdown hooks, when a new instance of the driver program might start just to tell the UPS to power off or to power-cycle)​.

It may be wise to ensure your OS name service client can cache the UPS name sufficiently long, or to use fixed IP addressing (and an entry in /etc/hosts for good measure, so you only have one spot to eventually re-configure this)​.